278 Rockwell Automation Publication 2198-UM002G-EN-P - February 2019
Chapter 7 Troubleshoot the Kinetix 5700 Drive System
Kinetix 5700 Status Indicators
These status indicators apply to the Kinetix 5700 DC-bus power supply, the
regenerative bus supply, the inverters, and the iTRAK® power supply. The
module status and network status indicators are just above the LCD status
display.
Table 123 - Module Status Indicator
Table 124 - Network Status Indicator
Table 125 - Ethernet Link Speed Status Indicator
Table 126 - Ethernet Link/Activity Status Indicator
IMPORTANT Status indicators are not reliable for safety functions. Use them only for
general diagnostics during commissioning or troubleshooting. Do not
attempt to use status indicators to determine operational status.
Condition Status
Steady Off No power applied to the drive.
Steady Green Drive is operational. No faults or failures.
Flashing Green Standby (drive not configured) and Precharge (drive is configured).
Flashing Red
Major recoverable fault. The drive detected a recoverable fault, for example, an incorrect
or inconsistent configuration.
Steady Red Major fault. The drive detected a non-recoverable fault.
Flashing Green/Red
Self-test. The drive performs self-test during powerup. Once self-test is complete,
Flashing Green/Red condition continues if drive is waiting for:
• Safety configuration when in Integrated STO mode
• Safety inputs when in Hardwired STO mode
Condition Status
Steady Off No power applied to the drive or IP address is not configured.
Flashing Green No Motion or Safety connection is established, but drive has obtained an IP address.
Steady Green
Motion or Safety connection is established and no timeout has occurred. Normal
operation.
Flashing Red
Connection timeout. One or more of the connections, for which this drive is the target,
has timed out.
Steady Red Duplicate IP address. IP address specified is already in use.
Flashing Green/Red
Self-test. The drive performs self-test during powerup. Once self-test is complete,
Flashing Green/Red condition continues if drive is processing a safety device ID proposal.
Condition Status
Steady Off 10 Mbit
Steady On 100 Mbit
Condition Status
Steady Off No link
Steady On Link established
Blinking Network activity
Module Status
Network Status
Kinetix 5700 Modules
Link Speed
Status Indicators
Ethernet RJ45 Connectors
Link/Activity
Status Indicators