M800S/M80/E80 Series Connection and Setup Manual
9 Connection of Operation Panel I/O Unit
268
IB-1501269-J
9.7 Connecting with Manual Pulse Generator (MPG)
Connect the manual pulse generator to MPG connector of the operation panel I/O unit.
Both 5V power supply type (UFO-01-2Z9) and 12V power supply type (HD60C) manual pulse generator can be used.
Take the maximum cable length, etc. into consideration when selecting.
(Note) Set one of the following parameters which is suitable for your manual pulse generator.
- 5V manual pulse generator (UFO-01-2Z9) : #1240 set12/bit0 = 1 (100 pulse/rev)
-12V manual pulse generator (HD60C) : #1240 set12/bit0 = 0 ( 25 pulse/rev)
(1) Connecting with 5V manual pulse generator (maximum cable length: 20m)
Connect the 5V manual pulse generator to the connector MPG.
MPG
NO.1
NO.1NO.2
NO.2NO.3 NO.1
5V0VAB
5V0VAB 5V0VAB
5V0VAB 5V0VAB 5V0VAB
J023
J024
J025
When connecting one 5V
manual pulse generator
When connecting two 5V
manual pulse generators
When connecting three
5V manual pulse
generators
Operation panel
I/O unit
5V manual pulse
generator
(Rear view)