Cause: The topology comparison has detected a controller extension 32 (CX32) in the actual topology that has been incorrectly
inserted with respect to the target topology.
Alarm value (r2124, interpret hexadecimal):
ddccbbaa hex:
dd = connection number (%4)
cc = component number (%3)
bb = component class (% 2)
aa = component number of the incorrectly inserted component (% 1)
Note:
The component is described in dd, cc and bb, where the component involved is incorrectly inserted.
Component class and connection number are described in F01375.
The drive system is no longer booted. In this state, the drive control (closed-loop) cannot be enabled.
Remedy: Adapting topologies:
- insert the components involved at the right connection (correct the actual topology).
- adapt the project/parameterizing in the commissioning tool (correct the target topology).
- automatically remove the topology error (p9904).
Note:
Under "Topology --> Topology view" the commissioning tool where relevant offers improved diagnostics capability (e.g.
setpoint/actual value comparison).
A01386 Topology: DRIVE-CLiQ component incorrectly inserted
Message value: Component: %1, to %2, %3, connection: %4
Drive object: All objects
Reaction: NONE
Acknowledge: NONE
Cause: The topology comparison has detected a DRIVE-CLiQ component in the actual topology that has been incorrectly inserted
with respect to the target topology.
Alarm value (r2124, interpret hexadecimal):
ddccbbaa hex:
dd = connection number (%4)
cc = component number (%3)
bb = component class (% 2)
aa = component number of the incorrectly inserted component (% 1)
Note:
The component is described in dd, cc and bb, where the component involved is incorrectly inserted.
Component class and connection number are described in F01375.
The drive system is no longer booted. In this state, the drive control (closed-loop) cannot be enabled.
Remedy: Adapting topologies:
- insert the components involved at the right connection (correct the actual topology).
- adapt the project/parameterizing in the commissioning tool (correct the target topology).
- automatically remove the topology error (p9904).
Note:
Under "Topology --> Topology view" the commissioning tool where relevant offers improved diagnostics capability (e.g.
setpoint/actual value comparison).
A01389 Topology: Motor with DRIVE-CLiQ incorrectly inserted
Message value: Component: %1, to %2, %3, connection: %4
Drive object: All objects
Reaction: NONE
Acknowledge: NONE
Faults and alarms
13.2 List of faults and alarms
SINAMICS S210 servo drive system
Operating Instructions, 12/2017, A5E41702836B AA 333

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SINAMICS S210 and is the answer not in the manual?

Siemens SINAMICS S210 Specifications

General IconGeneral
BrandSiemens
ModelSINAMICS S210
CategoryServo Drives
LanguageEnglish

Related product manuals