① Line filter (optional) ② Group terminals
Sum of the input currents of all converters per phase ≤ 24 A
● Fuses, F1 … F3
3NA3812 or class J 30 A for UL/CSA
● Cables for the connection from the terminal box to the converter
4 mm
2
, dimensioned for
I
rms
≥ 32 A at 50 °C
● Cables for the line connection up to the terminal box
2.5 mm
2
, dimensioned for
I
rms
≥ 18.5 A at 50 °C
Figure 3-6 Connection example for 400 V 3 AC