F37003 HF Damping Module: Damping voltage not established
Message value: %1
Drive object: All objects
Reaction: OFF2
Acknowledge: IMMEDIATELY
Cause: A damping voltage was not able to be established.
Fault value (r0949, interpret decimal):
Damping voltage in the case of a fault [mV].
Remedy: Check the HF Damping Module wiring.
F37004 HF Damping Module: Heat sink overtemperature
Message value: %1
Drive object: All objects
Reaction: OFF2
Acknowledge: IMMEDIATELY
Cause: The temperature of the heat sink in the HF Damping Module has exceeded the permissible limit value.
- insufficient cooling, fan failure.
- overload.
- ambient temperature too high.
Fault value (r0949, interpret decimal):
Temperature [0.01 °C].
Remedy: - check whether the fan is running.
- check the fan elements.
- check whether the ambient temperature is in the permissible range.
Notice:
This fault can only be acknowledged after the alarm threshold for alarm A05000 has been undershot.
Note:
HF Damping Module
F37005 HF Damping Module: I2t overload
Message value: %1
Drive object: All objects
Reaction: OFF2
Acknowledge: IMMEDIATELY
Cause: The filter capacitor of the HF Damping Module was overloaded (r5173 = 100 %).
- the filter resonance frequency was excessively excited.
- the HF Choke Module is defective.
Fault value (r0949, interpret decimal):
I2t [100 % = 16384].
Remedy: - reduce the motor power in the proximity of the fault-generating frequency.
- the system should not stay in a steady-state condition in the vicinity of the fault-generating frequency.
- check the HF Choke Module and if required replace.
Note:
HF Choke Module (reactor module)
HF Damping Module
F37012 HF Damping Module: Heat sink temperature sensor wire breakage
Message value: %1
Drive object: All objects
Reaction: OFF1 (OFF2)