Cause: A fault has occurred during the identification routine.
Fault value (r0949, interpret decimal):
10: Data set changeover during motor data identification.
101: Voltage amplitude even at 30% maximum current amplitude is too low to measure the inductance.
102, 104: Voltage limiting while measuring the inductance.
103: Maximum frequency exceeded during the rotating inductance measurement.
110: Motor not finely synchronized before the rotating measurement.
111: The zero mark is not received within 2 revolutions.
112:Fine synchronization is not realized within 8 seconds after the zero mark has been passed.
113: The power, torque or current limit is zero.
115: U/f control is active.
120: Error when evaluating the magnetizing inductance.
125: Cable resistance greater than the total resistance.
126: Series inductance greater than the total leakage inductance.
127: Identified leakage inductance negative.
128: Identified stator resistance negative.
129: Identified rotor resistance negative.
130: Drive data set changeover during the motor data identification routine.
140: The setpoint channel inhibits both directions.
160: Accelerating time when determining kT, moment of inertia or reluctance torque too short or too long.
161: When measuring the kT characteristic, constants kT1, kT3, kT5 and kT7 were not able to be determined (p0645 ...
p0648), as too few points were measured.
165: The current limit was reduced below the measurement current while determining the reluctance torque.
173: Internal problem.
180: identification speed (maximum speed, rated speed, 0.9 x p0348) less than p1755 or no DC link voltage available.
181: Zero speed at the end of the measurement of periodic position errors.
182: No complete mechanical revolution at to the end of the measurement of periodic position errors.
190: Speed setpoint not equal to zero.
191: An actual speed of zero is not reached.
192: Speed setpoint not reached.
193: Inadmissible motion of the motor when identifying the voltage emulation error.
194: Supplementary torque (r1515) not equal to zero.
195: Closed-loop torque control active.
200, 201: Not possible to identify the voltage emulation error characteristic of the drive converter (p1952, p1953).