3-47
Operation
Select Output_on/off. The System
asks you for the module and device
number of the device you wish to
energize or de-energize:
Type In Module & Device: -
Type the three-digit module number
and three-digit device number using the
numeric keypad and press ENTER.
The System offers you a choice of
arming or disarming the device:
Arm Disarm
Highlight your choice and press ENTER.
If you have armed the device, you can
press NEXT to display the number of
the next device in the sequence. You
can also press the Up arrow
(Ù) key to
return to the Control menu.
NOTE: You must first disarm a device if
you wish to energize or de-energize it.
When you disarm an output device, the
System automatically annunciates the
disarming as a Trouble and lights the
PARTIAL SYSTEM DISABLE LED.
If you choose to disarm an output
device, the System then asks if you
wish to energize it or de-energize it:
253-005 Energize De energize
Highlight your choice and press EN-
TER. Press NEXT to move through the
outputs until you display the ones you
want to change. Follow the instruc-
tions above for making the change.
When the System has displayed the
highest numbered device for the
module specified, it returns to the
Control menu. To arm or disarm and
energize or de-energize a device on a
different module, select Output_on/off
and follow the previous instructions.
Control: Loop_arm
Use Control Loop_arm to enable the
operation of a loop of ALD or XLD
initiating devices.
Select Loop_arm. The System asks
you for the module number of the ALD
or XLD loop you wish to arm:
Type In Module:
Type the three-digit module number
using the numeric keypad and press
ENTER.
The System makes the change. When
you arm input devices, the System
automatically annunciates the arming
as a Trouble OUT, and lights the
PARTIAL SYSTEM DISABLE LED.
Control: Loop_disarm
Use Control Loop_disarm to disable
the operation of a loop of ALD or XLD
initiating devices.
Select Loop_disarm. The System asks
you for the module number of the ALD
or XLD loop you wish to disarm:
Type In Module:
Type the three-digit module number
using the numeric keypad and press
ENTER.
The System makes the change. When
you disarm input devices, the System
automatically annunciates the disarm-
ing as a Trouble IN, and lights the
PARTIAL SYSTEM DISABLE LED.