MXL Trouble Messages
+15V Fault OCC-1 module defective, ZAC-30
module defective, OMM-1 pins shorted.
24 Volts on Battery Backup A PSR-1 has switched its 24V supply
to battery due to an AC failure or
brownout.
AC Fail or Brownout Primary AC power is missing or below
the brownout level; the System is
running on battery backup.
Airflow Too Low AnaLASER airflow is below programmed
threshold.
Airflow Too High AnaLASER airflow is above programmed
threshold.
Amplifier 1 Trouble Amplifier output, wiring from OCC-1
Amplifier 2 Trouble to amplifier input is incorrect.
Amplifier 3 Trouble
Amplifier 1 Backed Up Backup amplifier is active and
Amplifier 2 Backed Up described amplifier has failed.
Amplifier 3 Backed Up
Amplifier 1 Signal Loss  Riser wiring defective.
Amplifier 2 Signal Loss  ASC-1 switch setting is incorrect.
Amplifier 3 Signal Loss  Audio output from TBM-2 is not
present.
 ACM-1 or TBM-2 is defective.
 Wiring from TBM-2 to OCC-1 is
defective.
AnaLASER Power Trouble Problem with AnaLASER power supply.
Trouble Message The Probable Cause Is:
K-1
Appendix K
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens Cerberus PYROTRONICS MXL and is the answer not in the manual?

Siemens Cerberus PYROTRONICS MXL Specifications

General IconGeneral
BrandSiemens
ModelCerberus PYROTRONICS MXL
CategoryControl Panel
LanguageEnglish

Related product manuals