D - 1
Appendix D
Each MXL System enclosure requires a
power supply. This can be either an
MMB-2, PSR-1, PS-5A or PS-5N7. To
ensure that the power supply is not
overloaded, complete the worksheet
on the following page.
 Enter the quantity of each module
in the enclosure.
 Calculate both the 24V and 5V
loads for each row.
 Total the Active 24V and Active 5V
columns.
 Ensure that both totals are within
the power supply output ratings in
the table to the right.
MXL Power Supply Load
Calculations
POWER SUPPLY OUTPUT RATINGS
Module
Active 24 VDC Module
Current
Active 5 VDC Module
Current
MMB-2/MPS-6 6 amps 500mA
MMB-2/MPS-12 12 amps 500mA
PSR-1/MPS-6 6 amps 800mA
PSR-1/MPS-12 12 amps 800mA
PS-5A 0 amps 1 amp
PS-5N7 0 amps 500mA