1-5
Description
MMB-2 Main Board
The MMB-2 Main Board contains:
16-bit central processing unit (CPU)
System read-only memories
(EPROMs)
System random-access memory
(RAM)
FLASH memory for the CSG-M
Watchdog circuitry
Network interface circuitry (MNET)
Battery charger
24V regulator
AC transfer relay
Class A CZM-1B6 power
24 VDC unregulated supply
Two analog loops
(initiating/control)
Two notification appliance circuits
(audible/visual circuits)
Three dry-contact relays
MPS-6 Power Supply
The MPS-6 is a supervised power
supply that converts 120 VAC,
60 Hz to unregulated 24 VDC at 6A.
MPS-12 Power Supply
The MPS-12 is a high current power
supply that provides the MXL System
with primary 24 VDC power. It is rated
at 12 amps and is unfiltered and
unregulated. The MPS-12 supplies the
MMB-2 or PSR-1 and its expansion
modules with the power required for
normal operation. The module incorpo-
rates a 5 amp resettable circuit breaker
on the primary input, a 15 amp fuse on
the 24V output, and a built-in AC line
filter for surge and noise suppression.
The MPS-12 mounts in the MXL
enclosure backbox.
MMB-2 Main Board
MPS-6 Power Supply
MPS-12 Power Supply
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens Cerberus PYROTRONICS MXL and is the answer not in the manual?

Siemens Cerberus PYROTRONICS MXL Specifications

General IconGeneral
BrandSiemens
ModelCerberus PYROTRONICS MXL
CategoryControl Panel
LanguageEnglish

Related product manuals