J - 1
Appendix J
To ensure maximum safety, follow the
procedure described below. To ensure
proper and reliable operation, we
recommend the following inspection
and testing schedule:
Every Six Months
1. Check the sensitivity of each detec-
tor, using the List Sensitivity menu.
Refer to Appendix B - Device Analog
Voltages for a list of acceptable
detector sensitivity ranges.
2. If the PARTIAL SYSTEM DISABLE
LED is lit, check that all appropriate
detectors are armed, using the
Control Arm/Dis menu.
3. Activate a detector or alarm initiating
device. To test for Go/No Go opera-
tion, use
CERBERUS PYROTRONICS
TM
Test Gas, P/N 315- 282747, following
the instructions on the label. Check
that the detector LED lights and that
the proper indication is given at the
Control Panel.
4. Verify that an alarm can be acknowl-
edged and that the System can be
silenced and reset
5. Verify the time and date setting of
the System clock.
Testing
Every Year
1. Check that the System operates as
programmed by CSG-M and in
accordance with specifications.
2. Perform any other applicable tests
required by national or local fire
codes.
IMPORTANT
If the System is connected to the Fire Department, or activates an
external System (for example, a leased line connection), disarm the
related outputs before servicing to prevent activation. Notify persons
in the facility that you are conducting a System test so that they can
ignore any alarms that sound during testing. Be sure to reset the
System at the end of the inspection.