1-22
Description
TMM-1 Telephone Master Module
The optional TMM-1 Telephone
Master module provides firefighters
with an emergency telephone system
for communications with remote
locations. The TMM permits five
telephones to be off-hook at the same
time with almost no loss of quality in
the sound. This module also has a
wardens page feature that permits
paging through the speaker zones
from the master telephone as well as
from remote locations.
The push-to-talk button on the TMM-1
Telephone Master module connects
the red master telephone to the MXLV
System through the telephone riser.
It also provides the signal for the
wardens page.
MMM-1 Microphone Master Module
The MMM-1 Microphone Master
module provides firefighters with a
means of sending Voice messages to
the audio zones specified. The MMM-1
module has a push-to-talk switch on
the microphone, as well as a retract-
able coiled cord. Both are supervised.
A green LED on the MMM-1 indicates
when all selected zones are ready to
be paged.
VSM-1 Voice Switch and LED Module
The VSM-1 Voice Switch module
provides the system operator with
manual control and annunciation of the
MXLV System functions. Each VSM-1
has eight push-button switches; each
TMM-1 Telephone Master Module
MMM-1 Microphone Master Module
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens Cerberus PYROTRONICS MXL and is the answer not in the manual?

Siemens Cerberus PYROTRONICS MXL Specifications

General IconGeneral
BrandSiemens
ModelCerberus PYROTRONICS MXL
CategoryControl Panel
LanguageEnglish

Related product manuals