2 - 39
Installation
ZC1-8B S1 SETTINGS
Address 5 4 3 2 1 Address 5 4 3 2 1
ILLEGAL O O O O O 008 O X O O O
001 O O O O X 009 O X O O X
002 O O O X O 010 O X O X O
003 O O O X X 011 O X O X X
004 O O X O O ILLEGAL O X X O O
005 O O X O X ILLEGAL O X X O X
006 O O X X O ILLEGAL O X X X O
007 O O X X X ILLEGAL O X X X X
X=Closed or ON O=Open or OFF
Installing the ZC2-8B
The ZC2-8B plugs into a half-width slot
on the OMM and comes with an
installation kit that consists of the
following:
Eight end of line resistors,
P/N 140-820405
One 2A, 250V fuse,
P/N 105-292199
Eight 25V fuses, P/N 105-291200
One user key
Setting the Address on the ZC2-8B
Before installing the ZC2-8B in the
OMM, set the address on S1, DIP
switches SW1-SW4. Refer to the
CSG-M configuration printout for the
address of the module. Use the
ZC2-8B S1 Settings table to set the
address for this switch.
ZC2-8B Fuses
The ZC2-8B comes with 70V fuses,
P/N 105-291202, installed at the
factory.
For 25.2V Installations, remove the
70V fuses, F1-F8, and install the 25V
fuses, P/N 105-291200, found in the
installation kit.
Place the user key from the installation
kit in the OMM-1 card edge connector
for the ZC1-8B (between positions 37-
38 and 39-40).
After the address is set, install the
ZC1-8B in the OMM, being sure that
the module is riding in the card guides
and is firmly seated in the card edge
connector.
Location of the User Key for the ZC1-8B Switch S1 and Fuses F1-F8 on the ZC2-8B
ZC1-8B S1 SETTINGS