1-30
Description
ZC3-4AB
ZC Zone Control Card Modules
The Zone Control Card modules
provide a variety of audio/strobe input
channels and audio/strobe output
zones which enable the user to config-
ure the system to suit the specifica-
tions. All output zones are supervised,
power limited (with PLC-4 only), and
protected by fuses. The zone style is
either Class A (Style Z) or Class B
(Style Y), depending on the module
selected. The following table contains
the charac
teristics of all the zone
control cards.
ZC1-8B
ZC2-4AB
ZC2-8B
ZC Zone Control Card Modules
ZC ZONE CONTROL CARDS
Module
Audio
Channels
Audio
Outputs
Zone
Style
Audio
Input/Output
Rating Use
ZC1-8B with
25V fuses
18Style Y25V RMS
Speaker
and/or strobe
ZC1-8B with
70V fuses
1 8 Style Y 70.7V RMS Speaker only
ZC2-8B with
25V fuses
1 or 2 8 Style Y 25V RMS
Speaker or
strobe
ZC2-8B with
70V fuses
1 or 2 8 Style Y 70.7V RMS Speaker only
ZC2-4AB with
25V fuses
1 or 2 4
Style Y
or Z
25V RMS
Speaker or
strobe
ZC2-4AB with
70V fuses
1 or 2 4
Style Y
or Z
70.7V RMS Speaker only
ZC3-4AB with
25V fuses
1,2, or 3 4
Style Y
or Z
25V RMS
Speaker or
strobe
ZC3-4AB with
70V fuses
1,2, or 3 4
Style Y
or Z
70.7V RMS Speaker only
Technical Manuals Online! - http://www.tech-man.com