1-30
Description
ZC3-4AB
ZC Zone Control Card Modules
The Zone Control Card modules
provide a variety of audio/strobe input
channels and audio/strobe output
zones which enable the user to config-
ure the system to suit the specifica-
tions. All output zones are supervised,
power limited (with PLC-4 only), and
protected by fuses. The zone style is
either Class A (Style Z) or Class B
(Style Y), depending on the module
selected. The following table contains
the charac
teristics of all the zone
control cards.
ZC1-8B
ZC2-4AB
ZC2-8B
ZC Zone Control Card Modules
ZC ZONE CONTROL CARDS
Module
Audio
Channels
Audio
Outputs
Zone
Style
Audio
Input/Output
Rating Use
ZC1-8B with
25V fuses
18Style Y25V RMS
Speaker
and/or strobe
ZC1-8B with
70V fuses
1 8 Style Y 70.7V RMS Speaker only
ZC2-8B with
25V fuses
1 or 2 8 Style Y 25V RMS
Speaker or
strobe
ZC2-8B with
70V fuses
1 or 2 8 Style Y 70.7V RMS Speaker only
ZC2-4AB with
25V fuses
1 or 2 4
Style Y
or Z
25V RMS
Speaker or
strobe
ZC2-4AB with
70V fuses
1 or 2 4
Style Y
or Z
70.7V RMS Speaker only
ZC3-4AB with
25V fuses
1,2, or 3 4
Style Y
or Z
25V RMS
Speaker or
strobe
ZC3-4AB with
70V fuses
1,2, or 3 4
Style Y
or Z
70.7V RMS Speaker only
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens Cerberus PYROTRONICS MXL and is the answer not in the manual?

Siemens Cerberus PYROTRONICS MXL Specifications

General IconGeneral
BrandSiemens
ModelCerberus PYROTRONICS MXL
CategoryControl Panel
LanguageEnglish

Related product manuals