1-37
Description
Conventional
Detectors
The conventional devices described
below are available for use with the
MXL Control Panel. The UL identifiers
for compatibility are the same as the
model numbers.
DI-3 Ionization Detector
The DI-3 is an ionization detector for
use in open areas at altitudes of 0 to
4000 feet. It uses the DB-3S low
profile surface mounting base.
DI-3H Ionization High Altitude Detector
The DI-3H is an ionization detector for
use in open areas at altitudes of 3000
to 8000 feet. It uses the DB-3S low
profile surface mounting base.
DI-A3 Ionization High Air-Velocity
Detector
The DI-A3 is an ionization high air
velocity detector for use in open areas,
computer facilities, and air ducts at
altitudes of 0 to 4000 feet, with air
velocities of 0 to 1200 feet per minute.
It uses the DB-3S low profile surface
mounting base.
DI-A3H Ionization High Air-Velocity,
High Altitude Detector
The DI-A3H is an ionization high air
velocity, high altitude detector for use
in air ducts only at altitudes of 3000 to
8000 feet, with air velocities of 0 to
1200 feet per minute. It uses the DB-
3S low profile surface mounting base.
DI-B3 Ionization Air Duct Detector
The DI-B3 is an ionization detector for
use only in air ducts at altitudes of 0 to
4000 feet, with air velocities of 500 to
4000 feet per minute. It must be used
with a Series 3 air duct housing (AD-3I
or AD-3RI).
DI-B3H Ionization Air Duct High
Altitude Detector
The DI-B3H is an ionization detector for
use only in air ducts at altitudes of
3000 to 8000 feet, with air velocities of
500 to 4000 feet per minute. It must
be used with a Series 3 air duct hous-
ing (AD-3I or AD-3RI).
DT-11 Thermal Detector
The DT-11 is a thermal detector for use
in open areas. It uses the DB-11 low
profile surface mounting base or the
DB-3S base with the DB-ADPT
adapter.
PE-3 Photoelectric Detector
The PE-3 is a photoelectric detector
that responds to a wide range of both
flaming and smoldering fire conditions.
It uses either the DB-3S low profile
surface mounting base or the AD-3ILP
or AD-3XRILP air duct housing.
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens Cerberus PYROTRONICS MXL and is the answer not in the manual?

Siemens Cerberus PYROTRONICS MXL Specifications

General IconGeneral
BrandSiemens
ModelCerberus PYROTRONICS MXL
CategoryControl Panel
LanguageEnglish

Related product manuals