3-60
Operation
The System then sends information to
force this detector into pre-alarm. Once
it pre-alarms, or after a delay, the MXL
then restores the detector to its proper
pre-alarm setting.
Test: ASD_Devices
Use Test ASD_Devices to disable ASD
parameters and allow timely response
to test gas.
Select ASD_Devices and press ENTER.
The System tests the ASD devices
present in the System and displays the
following:
Testing Of ASD Device Enabled
Press ENTER again and the System
displays:
Testing Of ASD Device Disabled
Press ENTER to toggle between
Testing Enabled (Trouble In) and
Testing Disabled (Trouble Out). When
toggling between Testing Enabled and
Testing Disabled, there is a three
minute time period that separates the
two states.
Activating the ASD_Devices command
will post a Trouble into the System
which will be printed as:
TROUBLE IN 253 08:24:53 Aug 08, 20xx
#8- - - CERBERUS Pyrotronics---,
ASD Testing Enabled, MXL Panel
Pressing ENTER a second time will
cause the following message to be
printed out:
TROUBLE OUT 253 08:24:53 Aug 08, 20xx
#9- - - CERBERUS Pyrotronics---,
ASD Testing Disabled, MXL Panel
NOTE: If Test ASD_Devices is acti-
vated and left alone, the System will
automatically disable the test (time
out) after four hours. Test ASD_Devices
is inhibited while the System is initializ-
ing or resetting.
Test: Summarize
Use Test Summarize to ignore known
troubles, and instead view one summa-
rized trouble for an entire module. This
is typically used during installation and
commissioning.
Select Summarize and press ENTER.
The System displays the following
menu:
Select Mods ON OFF
Test: Summarize - Select_Mods
Use Test Summarize Select_Mods to
scroll through all installed (CSG-M)
module addresses and enable/disable
the summarize feature for each mod-
ule address. Choose Select_Mods and
press ENTER. The System displays
the following:
001 YES NO
Press NEXT and the System displays:
002 YES NO
The System flashes the currently
active summarize selection for the
module address. The operator may
then press the right
(Ø) or left (×)
arrow keys to highlight either YES or
NO and then press the ENTER key to
accept and program the selection.
When ENTER is pressed, the System
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens Cerberus PYROTRONICS MXL and is the answer not in the manual?

Siemens Cerberus PYROTRONICS MXL Specifications

General IconGeneral
BrandSiemens
ModelCerberus PYROTRONICS MXL
CategoryControl Panel
LanguageEnglish

Related product manuals