Page #151 background imageLoading...
Page #151 background image
3-52
Operation
Press NEXT to display the DC
output voltage:
007: DC Output = 26.5 Volts
Press NEXT to display the AC
voltage:
007: AC Voltage = 120.1 Volts
Press NEXT again to exit the Voltage
submenu.
Test: Power - Remote - Current
Select Current. The System shows
the battery charging current in amps:
007: Batt Chg Cur = 0.0 Amps
Press NEXT to display the DC
output current:
007: DC Output Cur = 0.1 Amps
Press NEXT again to exit the Current
submenu.
Test: Power - Remote - Options
Select Options. The System shows
the first option field, transformer size:
007: Transformer Size = 6 Amps
Press Next to display the next
option field, maximum battery charge:
007: Max Batt Chg = 3.0 Amps
Press NEXT to display the next
option field, tamper switch:
007: Tamper Enabled
Press NEXT again to exit the Options
submenu.
To print the PSR-1 voltages, currents,
and options, press the PRINT key
when the when the R in Remote is
blinking. The System will print informa-
tion in a format similar to the following:
Power Supply Statistics for PSR-1 7
at 10:49:37 Feb. 25, 20xx:
Batt Voltage < 27.2 volts Batt Chg Cur = 0.0 amps
DC Output = 26.5 volts DC Output Cur = 0.1 amps
Gnd Fault Reference = 11.4 volts
AC Voltage = 120.1 volts
Options selected: Transformer size = 6 amps
Max Batt Chg = 2.0 amps
Tamper Disabled
Test: MKB1_Lamptest
Use Test MKB1_Lamptest to test the
LEDs and the alphanumeric display on
the MKB.
Select MKB1_Lamptest and press
ENTER. The System displays the
following menu:
Lamp Test: LEDs Display
Test: MKB1_Lamptest - LEDs
Select LEDs and press ENTER to test
the LEDs and the audible on the MKB.
The LEDs light for 5 seconds and then
return to their previous state.
Test: MKB1_Lamptest - Display
Select Display and press ENTER to test
the alphanumeric display. The System
tests the display and then returns to the
MKB1_Lamptest menu.
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens Cerberus PYROTRONICS MXL and is the answer not in the manual?

Siemens Cerberus PYROTRONICS MXL Specifications

General IconGeneral
BrandSiemens
ModelCerberus PYROTRONICS MXL
CategoryControl Panel
LanguageEnglish

Related product manuals