Electrical ratings:
24VDC, 85mA
5VDC, 176mA
Electrical connections:
The ACM-1 can be wired in two
configurations:
1. Where an MMB-1/-2 (or PSR-1)
supplies the power and data com-
munications.
2. Where a PS-5N7 supplies the power
and data communications, as in a
remote expander board.
The wiring information below is unaf-
fected by whether the ACM-1 module
is in the upper or lower position of the
enclosure.
CAUTION:
Remember that all cables that connect to the ACM-1
are polarized and connect in one way only. DO NOT
FORCE THEM. The location of pin 1 on a connector is
indicated by marks on the pin or by color tracers on
the wires. In Nos.1 and 2 below, be sure the black
tracer wire is close to the 1.
1. To wire the ACM-1 in an enclosure
that has an MMB or a PSR.
Connect the long 15-conductor
ribbon cable (P/N 555-192238) from
the MMB-1/-2, P8 (or PSR-1, P5) to
P5 on the ACM-1.
Connect the short 15-conductor
ribbon cable (P/N 555-192242) from
the ANN-1, P1 to P4 on the ACM-1.
ACM-1 Connections and Ratings
4 - 1
Connect the 14-conductor ribbon
cable (P/N 555-192236) from the
TMM-1, P3 to P1 on the ACM-1, if
used.
Connect the 50-conductor ribbon
cable (P/N 555-192201) from the
TBM-1/-2, P3 to P2 on the ACM-1.
Connect the 5-conductor wire
cable (P/N 600-190220) from the
TBM-1/-2, P2 to P3 on the ACM-1.
P6 on the ACM-1 is connected to an
optional BTC-1 module, if used.
If an MMM-1 is used, connect the
9- conductor cable attached to the
MMM-1 to P7 on the ACM-1.
2. To wire an ACM-1 module when a
PS-5N7 is used to supply power and for
data communication (instead of an
MMB or a PSR):
Connect the long 15-conductor
ribbon cable (P/N 555-192238) from
the PS-5N7, P1 to P5 on the ACM-1.
Connect the 50-conductor ribbon
cable (P/N 555-192201) from the
TBM-1/-2, P3 to P2 on the ACM-1.
Connect the 5-conductor wire
cable (P/N 600-190220) from the
TBM-1/-2, P2 to P3 on the ACM-1.
Chapter
4
Connections and Ratings
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens Cerberus PYROTRONICS MXL and is the answer not in the manual?

Siemens Cerberus PYROTRONICS MXL Specifications

General IconGeneral
BrandSiemens
ModelCerberus PYROTRONICS MXL
CategoryControl Panel
LanguageEnglish

Related product manuals