Electrical ratings:
24VDC, 85mA
5VDC, 176mA
Electrical connections:
The ACM-1 can be wired in two
configurations:
1. Where an MMB-1/-2 (or PSR-1)
supplies the power and data com-
munications.
2. Where a PS-5N7 supplies the power
and data communications, as in a
remote expander board.
The wiring information below is unaf-
fected by whether the ACM-1 module
is in the upper or lower position of the
enclosure.
CAUTION:
Remember that all cables that connect to the ACM-1
are polarized and connect in one way only. DO NOT
FORCE THEM. The location of pin 1 on a connector is
indicated by marks on the pin or by color tracers on
the wires. In Nos.1 and 2 below, be sure the black
tracer wire is close to the 1.
1. To wire the ACM-1 in an enclosure
that has an MMB or a PSR.
Connect the long 15-conductor
ribbon cable (P/N 555-192238) from
the MMB-1/-2, P8 (or PSR-1, P5) to
P5 on the ACM-1.
Connect the short 15-conductor
ribbon cable (P/N 555-192242) from
the ANN-1, P1 to P4 on the ACM-1.
ACM-1 Connections and Ratings
4 - 1
Connect the 14-conductor ribbon
cable (P/N 555-192236) from the
TMM-1, P3 to P1 on the ACM-1, if
used.
Connect the 50-conductor ribbon
cable (P/N 555-192201) from the
TBM-1/-2, P3 to P2 on the ACM-1.
Connect the 5-conductor wire
cable (P/N 600-190220) from the
TBM-1/-2, P2 to P3 on the ACM-1.
P6 on the ACM-1 is connected to an
optional BTC-1 module, if used.
If an MMM-1 is used, connect the
9- conductor cable attached to the
MMM-1 to P7 on the ACM-1.
2. To wire an ACM-1 module when a
PS-5N7 is used to supply power and for
data communication (instead of an
MMB or a PSR):
Connect the long 15-conductor
ribbon cable (P/N 555-192238) from
the PS-5N7, P1 to P5 on the ACM-1.
Connect the 50-conductor ribbon
cable (P/N 555-192201) from the
TBM-1/-2, P3 to P2 on the ACM-1.
Connect the 5-conductor wire
cable (P/N 600-190220) from the
TBM-1/-2, P2 to P3 on the ACM-1.
Chapter
4
Connections and Ratings