Electrical ratings:
24 VDC, 78mA max
5 VDC, 33mA max
Outputs
Supervisory: 9 VDC, 9mA max
Activated: 12.5 VDC, 300mA max
End of line resistor:
10K, ¼W, ±1% (P/N 140-383467)
ZCT-8B Connections and Ratings
4 - 139
COMPATIBLE TELEPHONE UNITS
FT-301 Series Warden's Station
FT-302 Series Warden's Station
FJ-303 Jack
FJ-304 Jack/Terminal Block
Electrical connections:
All wiring must be in accordance with
Article 760 of NEC or the local building
codes.
Terminate all unused outputs with an
EOL resistor.