4 - 138
ZC3-4AB Connections and Ratings
ZC3-4AB Strobe Zone Wiring Diagram
NOTE:
ALL STROBE ZONE POLARITIES ARE SHOWN IN
SUPERVISORY CONDITION.
Strobe devices are not polarity supervised and
should be tested in compliance with NFPA
Standards.
24 VDC STROBE UNITS:
See Compatible Notification Appliances,
P/N 315-096363
ALL ZONES SUPERVISED, POWER LIMITED
Power Limiting is accomplished using the PLC-4 and
PL864-25A, -70A, or -25S as required. 24 VDC power
is available on the PLC-4.
All wiring must be in accordance with Article 760 of
NEC or the local building codes.
Maximum Loop Resistance:
3.0 ohms max, 1.5A
2.5 ohms max, 1.8A
Minimum Wire Size: 14 AWG
Supervisory Strobe Zone Connections
Supervisory: 1.5 VDC, 0.06mA
Activated: 24 VDC, 45 watts max (1.8A)
Maximum Total Load: 24 VDC
4.0A power limited
14.4A non-power limited
End Of Line Resistor: 24K, ½W, 5% (P/N 140-820405)
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens Cerberus PYROTRONICS MXL and is the answer not in the manual?

Siemens Cerberus PYROTRONICS MXL Specifications

General IconGeneral
BrandSiemens
ModelCerberus PYROTRONICS MXL
CategoryControl Panel
LanguageEnglish

Related product manuals