4 - 8
ASC-2 Connections and Ratings
ASC-2 Style Y Wiring Diagram
NOTES
1. All wiring must be in
accordance with
Article 760 of NEC or
the local building
codes.
2. Minimum wire size:
18 AWG twisted pair.
3. Maximum wire size:
14 AWG twisted pair.
4. High level amplifier
connections =
unshielded twisted
pair.
Low level amplifier
connections = shielded
twisted pair.
Other connections =
single conductor wire
5. Maximum rating:
25.2V RMS: 100W -
4.0A each input/output.
70.7V RMS: 100W -
1.4A each input/output.
6. Maximum loop length:
Refer to the decibel
loss tables.
7. The wire length
includes: The length of
the wire from the
ASC-2 to the amplifier,
the length of the wire
from the ASC-2 to the
ZC Series of audio
cards and back, and the
length of the longest
speaker zone served
by the amplifier.
8. End of Line device:
24K, ½W, 5%
(P/N 140-820405)
9. If there is no backup
amplifier, connect
terminals 3 and 4
together. If one backup
amplifier is shared by
more than one ASC-2,
connect all terminal 3s
together and leave the
terminal 4s unconnected.
10. Required for power
limited wiring.
*EOL is located at the last ZC Series or ICP audio card
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens Cerberus PYROTRONICS MXL and is the answer not in the manual?

Siemens Cerberus PYROTRONICS MXL Specifications

General IconGeneral
BrandSiemens
ModelCerberus PYROTRONICS MXL
CategoryControl Panel
LanguageEnglish

Related product manuals