InteliLite 9 Global Guide
159
Setpoint group Basic settings Related FW 1.1.0
Range [units] Enable/Disabled [-]
Default value Disabled Alternative config NO
Step [-]
Comm object 15889 Related applications AMF, MRS
Config level Advanced
Setpoint visibility Always
Description
This setpoint enables/disables filter values on CU screen and PC tools.
List of values which are filtered when filter is ON.
Generator Voltage L1-L2
Generator Voltage L2-L3
Generator Voltage L3-L1
Generator Voltage L1-N
Generator Voltage L2-N
Generator Voltage L3-N
Generator Frequency
Load kVA
Load kVA L1
Load kVA L2
Load kVA L3
Load kVAr
Load kVAr L1
Load kVAr L2
Load kVAr L3
Load kW
Load kW L1
Load kW L2
Load kW L3
Screen Filter
6 back to List of setpoints
Group: Engine settings
Subgroup: Starting