Value group Engine Related FW 1.1.0
Units RPM
Comm object 10123 Related applications AMF, MRS
Description
This value contains the current engine speed. The value is obtained from one of the following sources:
ECU, if an ECU is configured
Pickup input
Generator frequency
RPM
6 back to List of values
Value group Engine Related FW 1.1.0
Units %
Comm object 10137 Related applications AMF, MRS
Description
Engine speed control via CAN bus.
Speed request Requested speed Accelerator pedal position
0% 1350 RPM 0%
50% 1500 RPM 50%
100% 1650 RPM 100%
Speed Request
6 back to List of values
Value group Engine Related FW 1.1.0
Units RPM
Comm object 10006 Related applications AMF, MRS
Description
Requested engine speed.
Speed Required RPM
6 back to List of values
Group: Generator
Value group Generator Related FW 1.1.0
Units Hz
Comm object 8210 Related applications AMF, MRS
Description
Frequency of generator.
Generator Frequency
6 back to List of values