Alarm Type Shutdown
Alarmlist message Sd RPM Measurement Fail
Alarm evaluated During cranking
Related applications AMF, MRS
Description
The alarm is issued if the engine speed has not exceeded the Starting RPM (page
161) within the Maximum Cranking Time (page 160), although some of additional
running engine indication sources indicate that the engine has started.
Sd RPM Measurement Fail
6 back to List of alarms level 2
Alarm Type Shutdown
Alarmlist message Sd Short Circuit
Alarm evaluated All the time
Related applications AMF, MRS
Description
This is a fast overcurrent protection. The following setpoints are related to this
alarm:
Short Circuit BOC (page 193) adjusts the short current limit
Short Circuit BOC Delay (page 193) adjusts the delay in fine steps
Sd Short Circuit
6 back to List of alarms level 2
Alarm Type Shutdown
Alarmlist message Sd Start Fail
Alarm evaluated When the gen-set is being started
Related applications AMF, MRS
Description
This alarm will be issued after all attempts to start the gen-set have run out but the
gen-set did not start. The following setpoints are related to this alarm:
Cranking Attempts (page 160) adjust the number of attempts
Sd Start Fail
6 back to List of alarms level 2
Alarm Type Shutdown
Alarmlist message Sd Underspeed
Alarm evaluated Engine running only
Related applications AMF, MRS
Description
This alarm will be issued when the gen-set is running and then stops by itself, i.e.
the RPM drops under the value of setpoint Underspeed Sd (page 178).
The underspeed alarm starts to be evaluated after successful gen-set start and is
being evaluated for the entire time that the fuel solenoid is on.
Sd Underspeed
6 back to List of alarms level 2