InteliLite 9 Global Guide
382
Other type
Alarm Type BOC
Alarmlist message BOC Coolant Temperature
Alarm evaluated All the time
Related applications AMF, MRS
Description
This alarm indicates that the coolant temperature is higher than the temperature set
in Coolant Temperature Sd (page 182) setpoint.
BOC Coolant Temp
6 back to List of alarms level 2
Alarm Type BOC
Alarmlist message BOC Fuel Level
Alarm evaluated All the time
Related applications AMF, MRS
Description
This alarm indicates that the fuel level is lower than the level set level in Fuel Level
Sd (page 184) setpoint.
BOC Fuel Level
6 back to List of alarms level 2
Alarm Type BOC
Alarmlist message BOC + Name of analog input
Alarm evaluated All the time
Related applications AMF, MRS
Description
This alarm indicates that the value of general analog protection is out of BOC
protection limit.
BOC AIN Prot
6 back to List of alarms level 2
Alarm Type BOC
Alarmlist message BOC + Name of binary input
Alarm evaluated All the time
Related applications AMF, MRS
Description
Binary input also can be adjusted like alarm. In this case message in alarmlist
contains prefix - BOCand binary input name. This alarm occurs, when appropriate
binary input is active.
BOC BIN Protection
6 back to List of alarms level 2