Subgroup: Current Protection
Setpoint group Generator settings Related FW 1.1.0
Range [units] 100 .. 500 [%]
Default value 250 % Alternative config NO
Step
1 % of Nominal Current (page 146)
Comm object 8282 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
BOC occurs when generator current reaches this preset threshold.
Note: When there is no control of breakers, the type of protection is Sd not BOC.
Short Circuit BOC
6 back to List of setpoints
Setpoint group Generator settings Related FW 1.1.0
Range [units] 0,00 .. 10,00 [s]
Default value 0,04 s Alternative config YES
Step 0,01 s
Comm object 9991 Related applications AMF, MRS
Config level Advanced
Setpoint visibility Always
Description
Delay for Short Circuit BOC (page 193) protection.
Short Circuit BOC Delay
6 back to List of setpoints
Subgroup: Voltage Protection
Setpoint group Generator settings Related FW 1.1.0
Range [units]
Generator Overvoltage Wrn (page 194) .. 200 [%]
Default value 110 % Alternative config NO
Step
1 % of Nominal Voltage Ph-N (page 149) or Nominal Voltage Ph-Ph (page 149)
Comm object 8291 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
Threshold for generator overvoltage protection. All three phases are checked. Maximum out of three is used.
Note: Phase to phase and phase to neutral voltages are used for this protection.
Generator Overvoltage Sd