InteliLite 9 Global Guide
258
8.1.2 Values
What values are:
Values (or quantities) are analog or binary data objects, measured or computed by the controller, that are
intended for reading from the controller screen, PC, MODBUS, etc. Values are organized into groups according
to their meaning.
Invalid flag
If valid data is not available for a particular value, the invalid flag is set to it. This situation may be due to the
following:
The value is not being evaluated in the scope of the current application and configuration.
Sensor fail has been detected on an analog input.
The configured ECU or extension module does not provide the particular value.
The communication with the ECU or extension module is interrupted.
A value containing the invalid flag is displayed as “####” in InteliConfig and on the controller screen. If such a
value is read out via MODBUS, it will contain the data 32768 in the case of signed values and 65535 in the case
of unsigned values.
List of values groups
Group: Engine 261
Group: Generator 265
Group: Load 268
Group: Mains 273
Group: Controler I/O 275
Group: Statistics 276
Group: IL Info 279
Group: Log Bout 281
Group: CM-GPRS 284
Group: CM-4G-GPS 286
Group: CM-Ethernet 289
Group: Date/Time 292
Group: Plug-In I/O 292
For full list of setpoints go to the chapter List of values (page 259).