Related FW 1.1.0 Related applications AMF, MRS
Comm object 77
Description
This output is active when the generator voltage and frequency is within limits. It is deactivated:
immediately when the voltage/frequency gets out of limits (when GCB is not closed)
or
with an appropriate delay after the voltage/frequency has got out of limits (when GCB is closed)
Generator Healthy
6 back to Logical binary outputs alphabetically
Related FW 1.1.0 Related applications AMF, MRS
Comm object 1252
Description
This output is dedicated for diesel engine only. This output will close for exact time pre-set by setpoint Glow
Plugs Time (page 162) before every starting attempt. The output opens in same time as the STARTER (PAGE
344) output closes (100 ms after PRESTART (PAGE 341) output opens).
Image 8.35 Glow Plugs
Glow Plugs