EasyManuals Logo
Home>ComAp>Controller>InteliLite 9

ComAp InteliLite 9 User Manual

ComAp InteliLite 9
401 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #341 background imageLoading...
Page #341 background image
InteliLite 9 Global Guide
341
Related FW 1.1.0 Related applications AMF, MRS
Comm object 286
Description
Output has no function.
Not Used
6 back to Logical binary outputs alphabetically
LBO: P
Related FW 1.1.0 Related applications AMF, MRS
Comm object 36
Description
This output can be used for control of any device, which has to be activated just before start. The output is
closed for time period of Prestart Time (page 161). The output opens 100 ms before the STARTER (PAGE 344)
output closes.
Image 8.47 Engine start
Prestart