InteliLite 9 Global Guide
160
Setpoint group Engine settings Related FW 1.1.0
Range [units] 1 .. 10 [-]
Default value 3 Alternative config NO
Step 1
Comm object 8255 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
Maximal number of cranking attempts.
Cranking Attempts
6 back to List of setpoints
Setpoint group Engine settings Related FW 1.1.0
Fixed value 8 s
Description
Pause between Cranking Attempts (page 160). PRESTART (PAGE 341) output is active in this pause until
Cranking Fail Pause elapses.
IMPORTANT: This is a fixed parameter, it isn't possible to adjust it in any manner. This
parameter isn't visible either in controller or in PC tools.
Cranking Fail Pause
6 back to List of setpoints
Setpoint group Engine settings Related FW 1.1.0
Range [units] 1 .. 255 [s]
Default value 5 s Alternative config NO
Step 1 s
Comm object 8256 Related applications AMF, MRS
Config level Advanced
Setpoint visibility Always
Description
Maximum time limit of cranking time.
IMPORTANT: There is a protection against broken pinion on starter. In case that there are no
RPM after 5 seconds of starting, cranking is interrupted and cranking fail pause follows.
Maximum Cranking Time
6 back to List of setpoints