InteliLite 9 Global Guide
172
Subgroup: Starting Timers
Setpoint group Engine settings Related FW 1.1.0
Range [units] 0,0 .. 25,0 [s]
Default value 0,5 s Alternative config NO
Step 0,1 s
Comm object 10525 Related applications AMF, MRS
Config level Advanced
Setpoint visibility Always
Description
Delay between FUEL SOLENOID (PAGE 326) and STARTER (PAGE 344) logical binary inputs.FUEL SOLENOID
(PAGE 326) is closed before STARTER (PAGE 344). Lead time is adjusted via this setpoint.
Image 8.6 Fuel Solenoid Lead
Note: LBO PRESTART (PAGE 341) goes to logical zero when Fuel Solenoid Lead goes to logical one.
Fuel Solenoid Lead
6 back to List of setpoints
Setpoint group Engine settings Related FW 1.1.0
Range [units] 0 .. 600 [s]
Default value 12 s Alternative config NO
Step 1 s
Comm object 9097 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
Idle Time delay starts when RPM exceeds Starting RPM (page 161). Start fail is detected when during Idle
state RPM decreases below 2 RPM.
The output IDLE/NOMINAL (PAGE 335) remains inactive during the idle period. Binary output Idle/Nominal
opens during Cooling period again. This output can be used for switching the governor between idle and
nominal speed.
Idle Time