InteliLite 9 Global Guide
169
Setpoint group Engine settings Related FW 1.1.0
Range [units] 0 .. Prestart Time [s]
Default value 0 s Alternative config NO
Step 1 s
Comm object 15774 Related applications MRS. AMF
Config level Advanced
Setpoint visibility Only when LBO CHOKE (PAGE 322) is configured.
Description
This setpoint adjust the lead of logical binary output CHOKE. CHOKE (PAGE 322) is activated before logical
binary output STARTER (PAGE 344).
Note: In case Choke Lead is longer than 8s (cranking fail pause), Choke Lead will be limited to 8s
(cranking fail pause time). This limitation is applied only for cranking fail pause, Choke Lead in Prestart
stays unchanged.
Choke Lead
6 back to List of setpoints
Subgroup: D+ Functions
Setpoint group Engine settings Related FW 1.1.0
Range [units] Enabled / ChargeFail / Disabled [-]
Default value Disabled Alternative config NO
Step [-]
Comm object 9683 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
Behavior of D+ terminal.
Enabled The D+ terminal is used for both functions “running engine detection and charge fail
detection.
ChargeFail The D+ terminal is used for charge fail detection only
Disabled The D+ terminal is not used.
D+ Function