Setpoint group Engine settings Related FW 1.1.0
Range [units] 1..255 [s]
Default value 1 s Alternative config NO
Step 1 s
Comm object 14960 Related applications MRS. AMF
Config level Advanced
Setpoint visibility
Only if setpoint D+ Function (page 169) is not set to Disabled value.
Description
This setpoint adjusts delay for D+ function. This delay is used for:
Alarm Charging Alternator Fail.
For engine running condition - disengagement of starter
D+ Delay
6 back to List of setpoints
Setpoint group Engine settings Related FW 1.1.0
Range [units] No Protec/Wrn/Sd [-]
Default value Wrn Alternative config NO
Step [-]
Comm object 15751 Related applications MRS. AMF
Config level Advanced
Setpoint visibility
Only if setpoint D+ Function (page 169) is not set to Disabled value.
Description
This setpoint adjusts type of alarm Charging Alternator Fail.
D+ Alarm Type