InteliLite 9 Global Guide
200
Group: AMF settings
Subgroup: AMF Timers
Setpoint group AMF settings Related FW 1.1.0
Range [units] 0 .. 6 000 [s]
Default value 5 s Alternative config NO
Step 1 s
Comm object 8301 Related applications AMF
Config level Standard
Setpoint visibility
Conditioned by the setpoint Operation Mode (page 154)
Description
Delay after the mains failure to the start command of the gen-set.
Image 8.13 Emergency Start Delay
Emergency Start Delay
6 back to List of setpoints
Setpoint group AMF settings Related FW 1.1.0
Range [units] 1 .. 3 600 [s]
Default value 20 s Alternative config NO
Step 1 s
Comm object 8302 Related applications AMF
Config level Standard
Setpoint visibility
Conditioned by the setpoint Operation Mode (page 154)
Description
This setpoint adjust the delay, how long mains has to be returned after mains fail to start load transfer to
mains.
Mains Return Delay
6 back to List of setpoints