InteliLite 9 Global Guide
167
Setpoint group Engine settings Related FW 1.1.0
Range [units] 0,00 .. 20,00 [s/°C]
Default value 0,00 s/°C Alternative config NO
Step 0,01 s/°C
Comm object 15715 Related applications MRS. AMF
Config level Advanced
Setpoint visibility
Only when LBO CHOKE (PAGE 322) is configured and setpoint Choke Function
(page 165) = Temp Based.
Description
This setpoint adjust the maximal time of activation of binary output CHOKE (PAGE 322). Calculated time
depends on engine (coolant) temperature. Setpoint adjust curve which is used for calculating actual Choke
Time. When setpoint Choke Function (page 165) is set to Fixed Time value, setpoint Choke Increment has no
effect.
Note: If setpoint Choke Lead (page 169) is set to nonzero value, total time the CHOKE output is activated
still matches calculated value (based on actual temperature and setpoints Choke Increment and Choke
Start Temp (page 166)) This mean that adjusted parameters should ensure that calculated Choke Time
will be longer than Choke Leadto ensure expected Choke behavior.
Choke Increment
6 back to List of setpoints