InteliLite 9 Global Guide
326
Related FW 1.1.0 Related applications AMF, MRS
Comm object 22
Description
This output controls the fuel solenoid valve.
The output closes before binary output STARTER (PAGE 344).The lead time is adjusted by setpoint Fuel
Solenoid Lead (page 172).
Image 8.25 Fuel Solenoid 1
Image 8.26 Fuel Solenoid 2
The output opens when:
Emergency Stop comes
cooled gen-set is stopped
in pause between repeated starts
Fuel Solenoid
6 back to Logical binary outputs alphabetically