InteliLite 9 Global Guide
162
Setpoint group Engine settings Related FW 1.1.0
Range [units] 0,0 .. 10,0 [bar]
Default value 4,5 bar Alternative config NO
Step 0,1 bar
Comm object 9681 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
Oil pressure limit for starting. The controller will stop cranking (STARTER (PAGE 344) goes OFF) if the oil
pressure rises above this limit.
IMPORTANT: Value from analog input has higher priority than value from ECU.
Starting Oil Pressure
6 back to List of setpoints
Setpoint group Engine settings Related FW 1.1.0
Range [units]
0 .. Prestart Time (page 161) [s]
Default value 0 s Alternative config NO
Step 1 s
Comm object 14412 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
This setpoint defines the time before starting when logical binary output GLOW PLUGS (PAGE 332) will be
close.
Glow Plugs Time
6 back to List of setpoints