5.4.1 Start-stop sequence
State Condition of the transition Action Next state
Ready Start request
PRESTART (PAGE 341)
on
Prestart
Time (page 161)
counter started
Prestart
RPM > 2 or Oil pressure >
Starting
Oil Pressure (page 162)
or Generator
voltage > 10V or D+ voltage is
higher than
D+ Treshold (page 170)
Stop (Stop
fail)
OFF Mode selected or Shutdown
alarm active
Not Ready
Not Ready RPM < 2, Oil pressure not
detected, Generator voltage < 10V,
D+ not Active no shutdown alarm
active, other than OFF Mode
selected
Ready
Prestart Prestart time elapsed FUEL SOLENOID (PAGE 326) on,
STARTER (PAGE 344)
on,
Maximum
Cranking Time (page 160)
counter
started
Cranking
Cranking RPM > Starting RPM STARTER (PAGE 344) off, PRESTART
(PAGE 341) off
Starting
D+ input activated or oil pressure
detected or Generator voltage >
STARTER (PAGE 344) off, PRESTART
(PAGE 341) off
Cranking