InteliLite 9 Global Guide
211
Setpoint group General Analog Inputs Related FW 1.1.0
Range [units] the range is defined by analog sensor curve
Default value
the value is defined by
analog sensor curve
Alternative config NO
Step the step is defined by analog sensor curve
Comm object 9266 Related applications AMF, MRS
Config level Standard
Setpoint visibility Visible only if the logical analog input AIN PROT03 (PAGE 352) is configured
Description
Shutdown or BOC threshold level for AIN PROT03 (PAGE 352).
Note: These setpoints are used only if LAI AIN PROT03 (PAGE 352) is adjusted to required protection
type. Otherwise these setpoints are useless.
Analog Protection 3 Sd
6 back to List of setpoints
Setpoint group General Analog Inputs Related FW 1.1.0
Range [units] 0 .. 900 [s]
Default value 0 s Alternative config NO
Step 1 s
Comm object 9267 Related applications AMF, MRS
Config level Standard
Setpoint visibility Visible only if the logical analog input AIN PROT03 (PAGE 352) is configured
Description
Delay for AIN PROT03 (PAGE 352).
Note: These setpoints are used only if LAI AIN PROT03 (PAGE 352) is adjusted to required protection
type. Otherwise these setpoints are useless.
Analog Protection 3 Delay
6 back to List of setpoints

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliLite 9 and is the answer not in the manual?

ComAp InteliLite 9 Specifications

General IconGeneral
BrandComAp
ModelInteliLite 9
CategoryController
LanguageEnglish

Related product manuals