InteliLite 9 Global Guide
312
Related FW 1.1.0 Related applications AMF, MRS
Comm object 38
Description
Use this input to start and stop the gen-set in AUTO mode.
Note: If the binary input Remote Start/Stop is active and engine is running and mains failure occurs, the
MCB breaker opens, after Transfer Delay (page 201) the GCB breaker is closed. Once the mains is OK,
the Mains Return Delay (page 200) elapses and the GCB breaker is opened. Then after Transfer Delay
(page 201) is MCB breaker closed. Gen-set remains running as long as binary input Rem Start/Stop is
active. For more details see timing diagram below.
Image 8.22 Remote Start/Stop
Remote Start/Stop
6 back to Logical binary inputs alphabetically
Related FW 1.1.0 Related applications AMF
Comm object 61
Description
When input is closed, the controller automatically transfers load from the mains to the gen-set. Load is
automatically transferred back to the mains when any gen-set shut down protection activates.
Rem TEST On Load
6 back to Logical binary inputs alphabetically