InteliLite 9 Global Guide
168
Setpoint group Engine settings Related FW 1.1.0
Range [units] Disabled / 1–100 [%]
Default value Disabled Alternative config NO
Step 1 %
Comm object 15718 Related applications MRS. AMF
Config level Advanced
Setpoint visibility Only when LBO CHOKE (PAGE 322) is configured.
Description
This setpoint adjust threshold level for deactivation of CHOKE (PAGE 322) binary output. When generator
voltage is higher than this level, then logical binary output CHOKE is deactivated. In multiphase system it is
sufficient to deactivate CHOKE LBO when at least one voltage crosses this threshold. In case setpoint
Choke Voltage is set to Disabled value, no voltage is taken into account and CHOKE LBO isn't deactivated
on the voltage basis.
Choke Voltage
6 back to List of setpoints