InteliLite 9 Global Guide
165
Subgroup: Choke
Setpoint group Engine settings Related FW 1.1.0
Range [units] Disabled /Fixed Time / Temp Based [-]
Default value Disabled Alternative config NO
Step [-]
Comm object 15717 Related applications MRS. AMF
Config level Advanced
Setpoint visibility Only when LBO CHOKE (PAGE 322) is configured.
Description
This setpoint defines choke function behavior.
Disabled Choke function is disabled and logical binary output CHOKE (PAGE 322) is activated
under no circumstances.
Fixed Time
Choke time is fixedly defined by Choke Time (page 165) setpoint.
Temp Based
Choke time is calculated using actual engine (coolant) temperature. Setpoints Choke
Start Temp (page 166) and Choke Increment (page 167) are taken into consideration.
Choke Function
6 back to List of setpoints
Setpoint group Engine settings Related FW 1.1.0
Range [units] 0–3600 [s]
Default value 0 s Alternative config NO
Step 1 s
Comm object 13011 Related applications MRS. AMF
Config level Advanced
Setpoint visibility
Only when LBO CHOKE (PAGE 322) is configured and setpoint Choke Function (page
165) = Fixed Time.
Description
Defines time logical binary output CHOKE (PAGE 322) is activated for when fixed time is used. When setpoint
Choke Function (page 165) is set to Temp Based value, Choke Time value have no effect.
Note: If setpoint Choke Lead (page 169) is set to nonzero value, total time the CHOKE output is activated
still matches value set by Choke Time setpoint. This mean Choke Timeshould be longer than Choke
Leadto ensure expected Choke behavior.
Choke Time
6 back to List of setpoints