Image 8.53 Stop Solenoid 2
Note: If Additional running engine indications (page 102) are lost during 5s pause than Stop
Solenoid is not activated again otherwise stop solenoid is activated again.
6 Logical binary outputs alphabetically (page 315)
LBO: V
Related FW 1.1.0 Related applications AMF, MRS
Comm object 38
Description
This logical binary output is activated at the beginning of start procedure together with PRESTART (PAGE 341)
LBO. Ventilation output is deactivated when engine stops revolving.
Ventilation LBO is also deactivated immediately when EMERGENCY STOP (PAGE 305) (or E-Stop) is
activated or when controller is switched to OFF mode.
Note: The output is intended for control of an engine room ventilation fan, engine container ventilation
fan, container louvres or similar running gen-set technology.
Ventilation
6 back to Logical binary outputs alphabetically
Related FW 1.1.0 Related applications AMF, MRS
Comm object 2089
Description
This logical binary output is activated on rising edge of VENTILATION (PAGE 346) LBO (at the begining of
prestart period). The pulse duration is adjusted by Ventilation Pulse Time (page 191) setpoint.
Note: The output is intended for control of an engine room ventilation fan, engine container ventilation
fan, container louvres or similar running gen-set technology.
Ventilation On Pulse
6 back to Logical binary outputs alphabetically