Comm object 45
Description
The output controls the mains circuit breaker. Its state represents the breaker position requested by the
controller. The breaker must react within 5 seconds to a close or open command, otherwise an alarm is
issued.
Note: InteliLite 9 controllers can work even without breaker feedbacks, in this case do not configure the
feedback to binary inputs.
Image 8.39 MCB Close command
Image 8.40 Repeated MCB Close command
Image 8.41 MCB Open command