InteliLite 9 Global Guide
385
Alarm Type BOC
Alarmlist message BOC Generator < Frequency
Alarm evaluated Generator excited only
Related applications AMF, MRS
Description
This alarm evaluates the generator frequency in the phase L1. The following
setpoints are related to it:
Generator Underfrequency BOC (page 196)
Generator <> Frequency Delay (page 196)
BOC Generator < Frequency
6 back to List of alarms level 2
Alarm Type BOC
Alarmlist message BOC Overload
Alarm evaluated All the time
Related applications AMF, MRS
Description
The alarm is issued when the gen-set power is over the limit for time period longer
than the delay. The behavior of the overload alarm is adjusted by the following
setpoints:
Overload BOC (page 192) adjusts the overload limit.
Overload Delay (page 192) adjusts the delay
BOC Overload
6 back to List of alarms level 2
Alarm Type BOC
Alarmlist message BOC Short Circuit
Alarm evaluated All the time
Related applications AMF, MRS
Description
This is a fast overcurrent protection. The following setpoints are related to this
alarm:
Short Circuit BOC (page 193) adjusts the short current limit
Short Circuit BOC Delay (page 193) adjusts the delay in fine steps
BOC Short Circuit
6 back to List of alarms level 2
8.2.3 Fail sensor and other types
Fls AIN Prot 388
Fls Coolant Temp 388
Fls Fuel Level 388
Fls Oil Pressure 388
For full list of Fails sensor and other types of alarms go to List of fail sensor alarms (page 387).
What Fail sensor and other types of alarms are