InteliLite 9 Global Guide
361
Related applications AMF, MRS
Description
This alarm indicates that value the general analog protection is out of warning
protection limit.
6 back to List of alarms level 1
Alarm Type Warning
Alarmlist message Wrn + Name of binary input
Alarm evaluated All the time
Related applications AMF, MRS
Description
Binary input also can be adjusted like alarm. In this case message in alarmlist
contains prefix - Wrn and binary input name. This alarm occurs, when appropriate
binary input is active.
Wrn BIN Protection
6 back to List of alarms level 1
Alarm Type Warning
Alarmlist message Wrn Generator L1 > Voltage
Alarm evaluated Generator excited only
Related applications AMF, MRS
Description
This alarm evaluates the generator phase voltage in phase 1. The following
setpoints are related to it:
Generator Overvoltage Wrn (page 194)
Generator <> Voltage Delay (page 195)
Wrn Generator L1 > Voltage
6 back to List of alarms level 1
Alarm Type Warning
Alarmlist message Wrn Generator L1 < Voltage
Alarm evaluated Generator excited only
Related applications AMF, MRS
Description
This alarm evaluates the generator phase voltage in phase 1. The following
setpoints are related to it:
Generator Undervoltage Wrn (page 194)
Generator <> Voltage Delay (page 195)
Wrn Generator L1 < Voltage
6 back to List of alarms level 1
Alarm Type Warning
Alarmlist message Wrn Generator L1L2 > Voltage
Alarm evaluated Generator excited only
Wrn Generator L1L2 > Voltage