InteliLite 9 Global Guide
201
Setpoint group AMF settings Related FW 1.1.0
Fixed value 1.0 s
Description
Delay after GCB opening to MCB closing during the return procedure. Delay after MCB opening to GCB
closing if the setpoint Description (page 207) is set to GENRUN.
The time charts bellow show recommended setting of Transfer Delay setpoint.
If the Transfer Delay setpoint is set shorter than the time required for opening of the circuit breaker, the
controller closes GCB CLOSE/OPEN (PAGE 327) output straight away (100 ms) after the MCB FEEDBACK
(PAGE 309) input deactivates.
Image 8.14 Transfer Delay 1
If some delay between MCB FEEDBACK (PAGE 309) deactivation and closing of GCB CLOSE/OPEN (PAGE
327) output is required, then the Transfer Delay must be set to sum of MCB opening” + Delay time.
Transfer Delay