Image 4.19 Wiring of analog input with current sensor
0 - 22 mA
mA 0 1 2 3 4 5 6 7 8 9 10 11
Ω 100 133 167 202 241 283 328 375 431 489 553 625
mA 12 13 14 15 16 17 18 19 20 21 22
Ω 707 793 894 1007 1136 1287 1460 1666 1914 2222 2596
Note: This is a conversion of current from current sensor to appropriate resistance value. Use resistance
values in InteliConfig to create your specific curve. These values should be used in "Ohm" column.