InteliLite 9 Global Guide
195
Setpoint group Generator settings Related FW 1.1.0
Range [units] 0,0 .. 600,0 [s]
Default value 3,0 s Alternative config NO
Step 0,1 s
Comm object 9103 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
Delay for Generator Overvoltage Sd (page 193), Generator Overvoltage Wrn (page 194), Generator
Undervoltage BOC (page 194) and Generator Undervoltage Wrn (page 194) protection.
Generator <> Voltage Delay
6 back to List of setpoints
Subgroup: Frequency Protection
Setpoint group Generator settings Related FW 1.1.0
Range [units]
Generator Overfrequency Wrn (page 195) .. 200,0 [%]
Default value 110,0 % Alternative config NO
Step
0,1 % of Nominal Frequency (page 150)
Comm object 8296 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
Threshold for generator phase L1 overfrequency.
Note: When there is no control of breakers, the type of protection is Sd not BOC.
Generator Overfrequency BOC
6 back to List of setpoints
Setpoint group Generator settings Related FW 1.1.0
Range [units]
Generator Underfrequency Wrn (page 196) .. Generator Overfrequency BOC (page 195)
[%]
Default value 110,0 % Alternative config NO
Step
0,1 % of Nominal Frequency (page 150)
Comm object 9688 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
Threshold for generator phase L1 overfrequency.
Generator Overfrequency Wrn
6 back to List of setpoints