InteliLite 9 Global Guide
374
Shutdown
Alarm Type Shutdown
Alarmlist message Emergency Stop
Alarm evaluated All the time
Related applications AMF, MRS
Description
Alarm is activated when binary input EMERGENCY STOP (PAGE 305) is activated.
The gen-set shuts down in the moment the input is activated and starting is
blocked until the input is deactivated and fault reset is pressed.
Note: Use red emergency button placed on the switchboard door and connect
it to a binary input of the controller. Then configure the function Emergency
Stop to this binary input. It is recommended to use NC contact of the button.
Note: The MCB control is not affected by this alarm.
Emergency Stop
6 back to List of alarms level 2
Alarm Type Shutdown
Alarmlist message Sd Battery Flat
Alarm evaluated During cranking
Related applications AMF, MRS
Description
This alarm will be issued if the controller was reset during cranking of the gen-set.
If this situation occurs, the controller supposes the starting battery is so exhausted
that its voltage drops so low when starter motor is energized that it causes
controller reset.
Sd Battery Flat
6 back to List of alarms level 2
Alarm Type Shutdown
Alarmlist message Sd Coolant Temp
Alarm evaluated All the time
Related applications AMF, MRS
Description
This alarm indicates that the coolant temperature is higher than the temperature set
in Coolant Temperature Sd (page 182) setpoint.
Sd Coolant Temp
6 back to List of alarms level 2
Alarm Type Shutdown
Alarmlist message Sd ECU Communication Fail
Alarm evaluated
With configured LBO ECU POWER RELAY (PAGE 324) - only when this LBO is
active
Without configured LBO ECU POWER RELAY (PAGE 324) - all the time
Sd ECU Communication Fail